The Hawkeye 921 provides accurate load trending information with a proportional 4-20mA output signal.
Preset slide-switches provide easy field setup of sensed amperage range with no need for jumpers.
Applications: Load trending. Motor control. Fan/Pump Status. Loop powered analog current sensor simplifies installation. Power the sensor, and receive the signal with only two wires.
Lower cabling and commissioning costs than with traditional 3-wire sensors. Self-gripping split-core for fast retrofit installation.
Sensor Power 30mA (max)@12-30VDCInsulation Class 600VAC rms (UL) 300VAC RMS (CE)Frequency 50/60Hz Temperature Range -15° to 60°C (5° to 140°F)Humidity Range 10-90% RH non-condensingAccuracy ±2%FS from 10% - 100% of selected range but not less than ±0.4A Response Time 2 sec.Terminal Block Maximum Wire Size 14 AWGTerminal Block Torque (nominal) 4 in-lbs (0.45 N-m)Agency Approvals UL 508 open device listing CE: EN61010-1:2001-2 CAT III deg. 2 basic insulationFor applications requiring double or reinforced insulation please contact the factory.